FLN36-24KV H.V SF6 LBS 275mm

    FLN36-24KV H.V SF6 LBS 275mm

    FLN36-24KV indoor AC high-voltage sulfur hexafluoride load switch is suitable for three-phase AC 50Hz, rated voltage 24kV ring network power supply or double-radiation power supply system, used for closing and breaking load current and overload current, and can also be used for closing and breaking no-load long lines, no-load transformers and capacitor banks, etc. The series combination of load switch and current-limiting fuse can replace the circuit breaker, that is, the load switch is responsible for closing and breaking various load currents, while the current-limiting fuse is responsible f...
  • Share:
  • Contact us Inquiry

FLN36-24KV High Voltage SF6 Load Break Switch Spacing 275mm


FLN36-24KV indoor AC high-voltage sulfur hexafluoride load switch is suitable for three-phase AC 50Hz, rated voltage 24kV ring network power supply or double-radiation power supply system, used for closing and breaking load current and overload current, and can also be used for closing and breaking no-load long lines, no-load Transformers and capacitor banks, etc. The series combination of load switch and current-limiting fuse can replace the circuit breaker, that is, the load switch is responsible for closing and breaking various load currents, while the current-limiting fuse is responsible for breaking larger overload currents and short-circuit currents.


Operating environment


● Altitude: The maximum altitude of the equipment installation site is 1000m;

● Ambient air temperature: upper limit +40C, lower limit -15C;

● Ambient humidity: daily average relative humidity is not more than 95%, monthly average relative humidity is not more than 90%;

Earthquake: earthquake intensity does not exceed 8 degrees;

● Ambient air should not be obviously polluted by corrosive and flammable gases, water vapor, etc., and there should be no frequent severe vibrations.


Technical Specification


No.ItemUnitData
1Rated voltageKV24
2Rated frequencyHz50
3Rated currentA630
4Rated peak withstand currentKA50
54s rated short time withstand currentKA20
6Rated making currentKA50
7Rated breaking
current
Active load breaking currentKA630
Breaking current loopA630
Cable charging breaking currentA10
81  min power frequency withstand voltage(phase to
phase,to earth,fracture)
KV42/48
9Lightning impulse withstand voltage(phase to
phase,to earth,fracture)
KV75/85
10Relative pressure of SF6 gas(20°C Gp)MPa≤0.04
11Rated operating voltage (electric)VAC220、DC220
12Rated voltage of shunt releaseVAC220、DC220
13Average opening speedm/s3.5±1.5
14Average closing speedm/s3.5±1.5
15Three-phase points,closing phase of the samems≤3
16The main circuit resistanceμ Ω≤120
17Manual maximum torqueN.m≤160
18Phase to phase center distancemm210±0.5



Related tags:

ONLINE MESSAGE

Please fill in a valid email address
Captcha Can not be empty

RELATED PRODUCTS

No search results found!

Contact Information

Indiana Office

58Huaxing Road, industrial zone, Weng L ong Street Yueqing City, Zhejiang province, China.

+86-136-9571-0067

ansel@apexe.cc

Search

Insulation Accessories,Vacuum Circuit Breaker,Switchgear,High Voltage Electrical Equipment,Switchgear Fittings,Earthing Switch

This website uses cookies to ensure you get the best experience on our website.

Accept Reject